Call 248-619-9710
Quantity available: Call to check stock
Each 10 foot section of Square D's AP304G bus duct has ten plug-in ports, five each side, to accept PQ bus plugs.
This electrical busway is a great option for a manufacturer upgrading, expanding or replacing who need 400 amps available.
Reconditioned bus duct purchased from Legacy Industrial Electric comes ready for installation. Each section ships with all the connection hardware (joint pack, inspection covers, and hardware). We supply two HP3F hangers with each 10 foot section of busway.
Each section and component is inspected during reconditioning, and tested before it ships.
We back up our work with a one year replacement warranty.
We can help with system configuration.
A tap box is normally the first component of an electrical bus duct run to feed power from the distribution into the busway. The AP304G busway has three tap box options:
Bus plugs plug into the busway's plug-in ports to draw power while providing On-Off and over-current protection. The I-Line series has two over-current protection options for the bus plugs, fusible and circuit breaker.
The fusible PQ style bus plugs are the more common option.
Fusible PQ Bus Plugs for the AP304G bus duct.
Length: 120 inches
Height: 6 inches (side with bus plugs)
Width: 3.38 inches
Weight: 75 pounds
Bus Bar material: aluminum
The AP304G ships on a 12 foot skid by common carrier. To unload the busway a forklift is required. A loading dock is helpful. We can add the shipping charge to the quote.
Our standard lead time on a bus duct system over 100 feet is 10 working days. If a busway system requires customized components, or we need to acquire items, it may take longer.
Yes, if you have existing AP304G.
Yes. But... To run the bus duct vertically up a building requires vertical spring hangers to distribute the weight at each floor. Additionally, Square D makes a PS 200 amp bus plug for vertical applications. The standard PQ 200 amp bus plug cannot be used.
Legacy Industrial Electric LLC specializes in reconditioned busway systems. We can be reached at 248-619-9710, or by email at [email protected].